077 555 707 ↗
GEYA GYM9H-125-10kA High Breaking Miniature Circuit Breaker

GEYA

GYM9H-125-10kA High Breaking Miniature Circuit Breaker

Ավտոմատներ և պաշտպանիչներ։ GYM9H-125-10kA High Breaking Miniature Circuit Breaker։ Մոդելի տեխնիկական տվյալներ և գնառաջարկ ԲիգՎոլտից։

ԲրենդGEYA
Ապրանքային խումբԱվտոմատներ և պաշտպանիչներ

Տեխնիկական բնութագրեր

■ 10 kA Breaking Capacity Robust arc-chute and current-limiting contacts safely interrupt high fault currents typical of industrial distribution.■ Up to 125 A Continuous Heavy-duty bimetal + magnetic trip block designed for thermal stability at full load.
■ Dual Busbar Wiring Accepts both pin/fork comb busbars and cables up to 50 mm² — fast assembly in panels.■ Contact Position Indicator Mechanical window shows true contact state — important for lock-out / safe isolation.
■ B / C / D Curves One frame fits resistive, mixed, and motor / transformer inrush loads.■ Compact 18 mm/Pole DIN-rail (TH35-7.5) mounting — same modular width as standard 63 A MCBs.
ModelBreaking CapacityRated Current RangePolesCurvesTypical UseLink
GYM96 kA1 – 63 A1P / 2P / 3P / 4PB, C, DResidential final circuitsView GYM9 in Catalog→
GYM9H10 kA1 – 63 A1P / 2P / 3P / 4PB, C, DCommercial / light-industrial final circuitsView GYM9H-10kA →
GYM9H-12510 kA63 80 100 125 A1P / 2P / 3P / 4PB, C, DMain incomer, large feeders, industrial loads–
ParameterSpecification
Product ModelGYM9H-125
Rated Current (In)63, 80, 100, 125 A
Rated Voltage (Ue)240/415 V~ ; 230/400 V
Rated Insulation Voltage (Ui)500 V
Rated Impulse Withstand Voltage (Uimp)4 kV
Working Frequency50 / 60 Hz
Breaking Capacity (Icu)10,000 A (10 kA)
Number of Poles1P / 2P / 3P / 4P
Tripping CurvesB, C, D
Mechanical Life20,000 operations
Electrical Life10,000 operations
Wiring Capacity6 – 50 mm²
StandardsIEC/EN 60947-2, GB/T 14048.2
CertificationsCE, RoHS 2.0
Mounting35 mm DIN rail (TH35-7.5)
CurvesTest CurrentInitial StateTime (30 °C)Result
B, C, D1.13 InColdt ≥ 1 h (In ≤ 63) ; t ≥ 2 h (63 < In ≤ 125)No tripping
1.45 InThermalt < 1 h (In ≤ 63) ; t < 2 h (63 < In ≤ 125)Trip
2.55 InCold1 s < t < 120 sTrip
Ambient Temp.-20 °C-10 °C0 °C10 °C20 °C30 °C40 °C50 °C60 °C
Correction Factor1.251.201.151.101.051.000.950.900.85
PoleWidth (W)HeightDepth
1P18 mm89.5 mm80 mm
2P36 mm89.5 mm80 mm
3P54 mm89.5 mm80 mm
4P72 mm89.5 mm80 mm

BIGVOLT

Օգնե՞նք ընտրել։

Նշեք մոդելն ու ձեր էլեկտրական համակարգի պահանջները։

077-555-707 ↗
ք․ Երևան, Գլինկա 23/1