GEYA
GY-SVG-PLUS High-Spec Static Var Generator
Էլեկտրաէներգիայի որակ։ GY-SVG-PLUS High-Spec Static Var Generator։ Մոդելի տեխնիկական տվյալներ և գնառաջարկ ԲիգՎոլտից։
| Բրենդ | GEYA |
| Ապրանքային խումբ | Էլեկտրաէներգիայի որակ |
Տեխնիկական բնութագրեր
| Parameter | Specification |
| Model | GY-SVG-PLUS-220V | GY-SVG-PLUS-380V |
| Altitude | < 2000 m; above 2000 m, derate according to GB/T 3859.2 |
| Ambient Temperature | -10 °C ~ +50 °C (above 40 °C, capacity derating ≤ 30%) |
| Relative Humidity | ≤ 90% RH, no condensation on the surface at a monthly minimum temperature of 25 °C |
| Pollution Degree | ≤ Class III |
| Operating Voltage | 220V model: AC 220 V (-20% ~ +20%) 380V model: AC 380 V (-20% ~ +20%) |
| Operating Frequency | 50 Hz / 60 Hz (45 Hz ~ 63 Hz) |
| Rated Compensation Capacity | 220V model: 37 kvar, 50 kvar 380V model: 75 kvar, 100 kvar |
| Grid Configuration | Three-phase three-wire (3P3W) / Three-phase four-wire (3P4W) |
| Number of Parallel Units | Unlimited |
| Overall Efficiency | ≥ 97% |
| Switching Frequency | 16 kHz |
| Function Selection | Reactive power compensation / Reactive power compensation + three-phase unbalance compensation |
| Reactive Compensation Rate | Reactive power compensation ≥ 99% |
| Unbalance Compensation Capability | Unbalance degree after compensation ≤ 5% |
| Full Response Time | < 10 ms |
| Noise Level | ≤ 65 dB |
| Communication Method | 2× RS485 communication ports (Wi-Fi supported) |
| Protection Functions | Overload, software/hardware overcurrent, grid overvoltage/undervoltage, grid voltage unbalance, power supply failure, over-temperature, frequency anomaly, short circuit protection, resonance protection, etc. |
| Overload Capability | Rated 1.2× overload for 60 seconds |
| Installation Method | Rack-mounted / Wall-mounted |
| Cable Entry | Rear cable entry (rack-mount) / Top cable entry (wall-mount) |
| Protection Rating | IP20 (IP54 customizable) |
| Neutral Line Filtering Capability | Neutral line filtering capacity is 3 times that of phase filtering capacity |
| Cooling Method | Forced air cooling |
| Electromagnetic Compatibility | EMC – Radiated Emission (RE) and Conducted Emission (CE) meet Class A test standard |
077 555 707 ↗