GEYA GY-AVC-PLUS Unified Power Quality Control Device

GEYA

GY-AVC-PLUS Unified Power Quality Control Device

Էլեկտրաէներգիայի որակ։ GY-AVC-PLUS Unified Power Quality Control Device։ Մոդելի տեխնիկական տվյալներ և գնառաջարկ ԲիգՎոլտից։

ԲրենդGEYA
Ապրանքային խումբԷլեկտրաէներգիայի որակ

Տեխնիկական բնութագրեր

ParameterSingle-Phase (220V)Three-Phase (380V)
Rated Power30kVA30kVA~500kVA
Rated Current135A45A~750A
Rated VoltageAC220VAC380V
Voltage Range-40%~+30%
Rated Frequency50Hz/60Hz
Grid StructureL/N+PEThree-phase four-wire +PE
AC Overload Capability1.1 times the duration
Output Voltage Accuracy±1%
Function SelectionVoltage compensation + (reactive power compensation, harmonic compensation, reactive + harmonic compensation)Voltage compensation + (reactive, harmonic, three-phase unbalance, reactive + harmonic, reactive + unbalance, reactive + unbalance + harmonic compensation)
Compensation Voltage RangeAC380 ±20% (-40%~+30% customizable)
Transformer Ratio5:1
Harmonic Compensation Rate3-13th comprehensive harmonic compensation ≥95%
Reactive Power Compensation RateReactive power compensation ≥99%
Three-Phase Unbalance Compensation Rate/Unbalance degree after compensation ≤5%
Allowable Grid Frequency45~63Hz
Output Voltage THD Increment≤1%
Compensation Response Time<20ms
ParameterSingle-PhaseThree-Phase
Rated Capacity6kVA6kVA~100kVA
TypeDry type, magnetic core made of stacked silicon steel sheets, frame grounded
Overload Capability1.1 times longer running time
InsulationInsulation level H
Transformation Ratio220:44
Design TemperatureTemperature rise ≤90K
Applicable StandardIEC 726
Altitude<2000m; above 2000m, use in accordance with GB/T 3859.2 for derating
Ambient Temperature-10~+50°C (reduced capacity above 40°C)
Relative Humidity90%, monthly minimum temperature 25°C, no condensation on the surface
Pollution DegreeBelow Level I
Noise Level≤70dB
Degree of ProtectionIP20 (IP54 customizable)